Why is the ROOM Booth compliant for omission of integration to the fire alarm system interface?

The building fire alarm signaling system must be arranged to produce a sound level at least 15 decibels (dBA) above the average ambient sound level; the pod system needs to be tested to show that the building fire alarm system can provide the required sound levels inside of the pod with the roof intact (closed).

If the pods are only used for employee use areas, a strobe notification appliance is not needed unless the employees in the space are hearing impaired. Since the 2006 edition of the IBC, a 20-percent spare capacity is required to be built into the building fire alarm system to add strobes if needed. If required, the strobe appliance can be located outside of the pod if the strobe light is able to penetrate into the space. The penetration of light can be through glass side panels via a wall mounted appliance or through the transparent door via a wall mounted appliance. skylight roof via a ceiling mounted appliance. Alternatively, NFPA 72 allows for a performance-based alternative to visible notification appliance location, provided it is proven that the design allows a minimum illumination of 0.0375 lumens/ft2 at any point within the pod at all angles.

Please reach out to us at support@room.com if you have additional questions.

Your Cart
Your cart is empty
Estimated Total:
Monthly Payment:
We just need a bit more information.
We'll be with you soon!

A ROOM representative will reach out soon via email. Feel free to take a look around while you wait.

Close
Taxes and Shipping calculated at checkout